Glow T180
Tankless Condensing Water Heater
57
Lockout
Codes
Description Resolution
A24 Blocked flue switch is open
* Follow instruction given in flowchart: A24 Block flue switch
open
A29 Internal software error
* Recycle power and press RESET
* If lockout code still exists, replace ICB and display board
A30 Internal software error
* Recycle power and press RESET
* If lockout code still exists, replace ICB and display board
Press RESET to restore unit to normal operating mode
Blocking
Errors
Description Resolution
E100
E101
E102
E103
E104
E106
E107
E108
E109
E110
E111
E112
E113
E114 Flame is detected and not present
* Power OFF the unit and clean ionization electrode
* Recycle power and press
RESET
* Allow the burner to operate at high fire for 1 minute if E114 still
appears replace the ICB
* Recycle power and press RESET
E119
DCW inlet sensor failure * Follow instruction in flowchart: E119 DCW inlet sensor failure
E120 Heat exchanger outlet sensor failure
* Follow instruction in flowchart: E120 heat exchange outlet
sensor failure
E122
DHW outlet sensor failure * Follow instruction in flowchart: E122 DHW outlet sensor failure
E123
Flue sensor failure * Follow instruction in flowchart: E123 flue sensor failure
E126 DCW sensor shorted
* Recycle the power
* If E126 BLOCKING ERROR still exists, replace DCW inlet
sensor
E127 Heat exchanger outlet sensor shorted
* Recycle the power
* If E127 BLOCKING ERRORstill exists, replace heat exchanger
outlet sensor
E129 DHW sensor shorted
* Recycle the power
* If E129 BLOCKING ERROR still exists, replace DHW outlet
sensor
E130 Flue sensor shorted
* Recycle the power
* If E130 BLOCKING ERROR still exists, replace flue sensor
E134 Too many RESETs in a short time period
* Power OFF unit, wait 5 minutes, Power ON unit
* If E134
BLOCKING ERROR still exists, replace ICB and display
board
E135 Incorrect polarity
* Power OFF the unit
* Check and reverse the polarity at the receptacle
Internal software error
* Recycle power and press
RESET
* If BLOCKING ERROR still exists, replace ICB and display
board