8. Installation
5.
The go-e Charger is equipped with an integra-
ted RCD protection module with direct current
detection (20 mA AC, 6 mA DC).
Only a type A RCD is required on the building
side, unless local regulations deviate from this.
In addition, a miniature circuit breaker must be
installed upstream.
Miniature circuit breakers with characteristic B
or C for 16 or 32 amperes are permissible:
• 3- or 4-pole for three-phase connection
• 2-pole for single-phase connection
6.
When installing multiple units, activate static
load balancing via the go-e Charger app (WiFi
required).