8. Installation8. Installation
5.
The go-eCharger is equipped with an integrated
RCD protection module with direct current detec-
tion (30 mA AC, 6 mA DC).
Only a type A RCD is required on the building side,
unless local regulations deviate from this. In ad-
dition, a miniature circuit breaker must be installed
upstream.
Miniature circuit breakers with characteristic B or
C for 16 or 32 amperes are permissible:
3- or 4-pole for three-phase connection
2-pole for single-phase connection
9. Installation9. Installation
6.
The go-eCharger HOMEx may be connected
single-phase and three-phase. If necessary, lay an
additional supply line. When selecting the cable
cross-section, observe the simultaneity factor and
the type of installation. We recommend the follo-
wing cable cross-sections, but the electrician has
to decide according to local conditions:
HOMEx 11 kW HOMEx 22 kW
as surface-
mounted
at least 2.5 mm² at least 6 mm²
in wall at least 4 mm² at least 6-10 mm²
in insulation at least 10 mm² at least 10 mm²
The connection cable of the go-eCharger HOME-
x may also be shortened. Connection via a junc-
tion box is possible.
7.
When installing several devices, connect the
phases of the rst, second and third charger to
the domestic circuit in rotation according to the
adjacent illustration to ensure even load distribution
when charging single-phase vehicles.
Activate static load balancing via the go-eCharger
app (WiFi required).