gpelectric.com | [page 17]
17. Clear SOC Relay
When the state-of-charge percentage has risen above this value, the relay will open (after a delay, depending on
setting 14 and/or 15). This value needs to be greater than the previous parameter setting. When the value is equal
to the previous parameter the state-of-charge percentage will not close the relay.
Default Range Step Size
90% 0-99% 1%
18. Low Voltage Relay
When the battery voltage falls below this value for more than 10 seconds the relay will close.
19. Clear Low Voltage Relay
When the battery voltage rises above this value, the relay will open (after a delay,depending on setting 14 and/or
15). This value needs to be greater than or equal to the previous parameter.
20. High Voltage Relay
When the battery voltage rises above this value for more than 10 seconds the relay will close.
21. Clear High Voltage Relay
When the battery voltage falls below this value, the relay will open (after a delay, depending on setting 14 and/or
15). This value needs to be less than or equal to the previous parameter.
GP-BMK-50
Default Range Step Size
0V 0-95V 0.1V
22. Low Starter Voltage Relay
When the auxiliary (e.g. starter battery) voltage falls below this value for more than 10 seconds the relay will be
activated.
23. Clear Low Starter Voltage Relay
When the auxiliary voltage rises above this value, the relay will open (after a delay,depending on setting 14 and/or
15). This value needs to be greater than or equal to the previous parameter.
24. Higher Starter Voltage Relay
When the auxiliary (e.g. starter battery) voltage rises above this value for more than 10 seconds, the relay will be
activated.
FULL SET-UP DETAILS