SmartBox
®
4 / SmartBox
®
4 PRO
part no. 28 400 57 d 15 / 28
EXAMPLES FOR PROGRAMMING
Example 1: Basement tank for 6,000 litres heating oil, linear steel tank
Inner height 165cm, (fill level 125cm)
SmartBox
®
4 with standard levelprobe 0 - 250mbar
Step
Entries / selection
PIN
PIN: 0000 (set with [+] key
press [Enter] to save)
1.Measure probe
250mbar
2.Liquid
Heat.oil
3.Tank shape
Linear
4.Tank volume
6.000L (set with [+] / [-] keys)
5.Tank height
165.0cm (set with [+] / [-] keys)
5b.Filling limit
95%=157cm (set with [+] / [-] keys)
6.View View details
Fillspace+Percnt
(2st line of the display set with [+] / [-] keys)
7.Relay
Deactive
8.Exit
press [Enter] to see the indication
Heat.oil 4.550L
-1.150L 76%
Example 2: Buried tank, cylindrical, horizontal, for 100,600 litres diesel oil
Inner height 2.886m, (fill level 54cm)
SmartBox
®
4 with standard levelprobe 0 - 250mbar The
relay to be used as an dry-run protection for a pump
Relay
- On at > 11% - Off at < 10%
Step
Entries / selection
PIN
PIN: 0000 (set with [+] key
press [Enter] to save)
1.Measure probe
250mbar
2.Liquid
Diesel (set with [+] / [-] keys)
3.Tank shape
Cylindric horiz (set with [+] / [-] keys)
4.Tank volume
100.600L (exact value from volume table,
set with [+] / [-] keys)
5.Tank height
288.6cm (exact value from volume table,
set with [+] / [-] keys)
5b.Filling limit
97%=279cm (set with [+] / [-] keys)
6.View View details
Fillspace+Percnt
2st line of the display
set with [+] / [-] keys)
7.Relay Active Limiting
tank:1
Switch-on: 11% Switch-off: 10%
(set with [+] / [-] keys)
6.Exit
press [Enter] to see the indication
Diesel 12.800L
-84.800L 13%