SmartBox
®
4 / SmartBox
®
4 PRO
22 / 28 part no. 28 400 57 d
number for the
SMS
Mobile phone number to which the
automatically generated reporting SMS are
sent (e.g. building supervisor, headquarters)
(identic
al to
#TA=)
phone number
for alarms
1. Mobile phone number for a fault mobile
phone. If for #TA1=... an alarm number is
entered, the alarm SMS is sent to this number
(approx. 5-minute delay).
If no number is entered (field empty), the
report is sent to the #T number.
Inspector
connection
exists, this
field is empty
…
#TA3=
phone number
for alarms
2. + 3. Mobile phone number for a fault
mobile phone. The current alarm is reported to
this number as 2. / 3. (for delay time, see
command #Q= ) If this alarm number is not
entered (empty), this means that the end of the
alarm chain has been reached and that there
are no further messages for this alarm.
Inspector
connection
exists, this
field is empty
Change the delay time for the alarm chain, e.g.
#Q=10 sets the delay time to 10 minutes.
Header-Text, introducing every SMS
message.
(always enter
4 values as 2-
digit figures,
preceded by 0
if necessary!)
Fill level message points:
1 =
Percentage increment for new
message, e.g. report fill level after
[01..99] %
2 =
Period of days for new message,
e.g. send a report on the system
min. every 30 days. Or indicate
number of hours with xxh. Add ‘h’
to indicate a number of hours.
[01..99] Tg
[01h..24h]
3 =
’Critical limit value’ in per cent, i.e.
if the value falls below the limit, an
[00..99] %
4 =
Interval of days for repeating the
message on limit value.
[01..31] days
10,30,15,07,
0,5,0
5 =
0 Triggers a limit value report as
soon as one of the tanks reaches
the reserve level.
1 Triggers a limit value report only
when all of the tanks reach the
maximum level.
2 Triggers a limit value report as
soon as one of the tanks reaches
the reserve level.
3 Triggers a limit value report only
when all of the tanks reach the
[0 to 3]