SmartBox
®
4 / SmartBox
®
4 PRO
part no. 28 400 57 d 23 / 28
Comm-
and
Parameter
Description
Standard /
default value
6. Value:
10,03,15,07,
0,5,0
Number
6 =
Percentage for increase in content,
that triggers a fuelling report, e.g.
5%
5
[01..99] %
7. Value:
10,03,15,07,
0,5,0
Number
7 =
1 or 0. With 1, in a fuelling case a
message with the initial value is
displayed.
0
[0 oder 1]
#Pn=
#P Change
parameters
individually
The above #P parameters can also be set
individually: e.g. #P6=8 or #P2=36h
#A1=
Configure
alarm 1: 0,
"Text"
Configuration: 0 (alarm, when contact closed)
1 (alarm, when contact open)
Additional text: e.g
.: Boiler cold
(max. 15 signs)
0, system
fault
#G=
0 - 101
Activate credit information:
9
0=
OFF, no credit information, contract
card or other prepaid-SIM-card
1=
ON for prepaid-SIM-card T-Mobile
(*100# - in Germany)
2=
ON for old prepaid-SIM-card Vodafone
(**100# - in Germany)
9=
SMS counter (recommended for
contract SIM-card!)
101=
106=
ON for Prepaid-SIM-card O
2
(*101# -
in Germany)
ON for new prepaid-SIM-card
Vodafone (**106# - in Germany)
#Ni=
Enter name for
tank i
#N1=Name Tank1 (the name of the tank can
have up to 16 characters)
#N1=… to
#N4=…
#LG=
Language
#LG=0 sets language to German, 1 to English
2 to ’French’, 3 to ’Spain
#LG=0,#LG=1
#LG=2,#LG=3
#TMPn=
Temperature
limit value n =
tank number
Set temperature limit value in °C e.g.:
#TMP1=18#TMP2=5#TMP3=-10#TMP4=-99
Value -99 = Deactivation
The lower deviation causes a temperature
alarm in alarm chain #TA1...#TAn
-99
[-99..99] °C
#I2
#I3
#I4
Delete tank:
The tank with this number is deleted from the
tank registry. The tank numbers behind this
move up one place.
(The previous command #I deleted all tanks).
only
SmartBox
®
4
#I98
Remote reset: Cold start command for
processor and modem