10 Technical Parameters
37
User Manual V1.0-2022-12-15
Maximum Output
Overcurrent Protection
(A)
42 42 42 42 42 50
Eciency
Max. Eciency 96.0% 97.8% 97.8% 97.8% 97.8% 97.8%
European Eciency 95.6% 97.5% 97.5% 97.5% 97.5% 97.5%
Protection
PV Insulation Resistance
Detection
Integrated
Residual Current
Monitoring
Integrated
PV Reverse Polarity
Protection
Integrated
Anti-islanding Protection
Integrated
AC Overcurrent
Protection
Integrated
AC Short Circuit
Protection
Integrated
AC Overvoltage
Protection
Integrated
DC Switch Optional
DC Surge Protection Type III(Type
II Optional)
Type III Type III Type III Type III Type III
AC Surge Protection Type III
Emergency Power O Optional
Remote Shutdown Optional
General Data
Operating Temperature
Range (℃)
-25 - +60
Relative Humidity 0 - 100%
Max. Operating Altitude
(m)
*5
4000
Cooling Method Natural Convection
User Interface LED,LCD,WLAN+APP
Communication WiFi,RS485 or 4G or 2G or LAN (Optional)
Weight (kg) 13.0 13.0 13.0 13.0 13.0 13.5
Dimension (W×H×D mm) 354 × 433 × 147
Noise Emission (dB) < 25 < 25 < 25 < 25 < 25 < 50
Topology Non-isolated
Self-consumption at
Night (W)
<1
Ingress Protection
Rating
IP65