10 Technical Parameters
39
User Manual V1.0-2022-12-15
Max Power at 40℃ (including AC
overload)(W)(For Brazil only)
3000 3680 4200 5000 6000
Nominal Output Voltage (V) 220/230 220/230 220/230 220/230 220/230
Nominal AC Grid Frequency (Hz) 50/60 50/60 50/60 50/60 50/60
Max. Output Current (A) 13.6 16.0 19.0 22.8 27.3
Max. Output Fault Current (Peak
and Duration) (A)
35 35 35 35 35
Inrush Current (Peak and
Duration) (A)
60 60 60 60 80
Nominal Output Current (A) 13.6/13.0 16.0/15.6 19.0/18.2 22.8/21.7 27.3/26.1
Power Factor ~1 (Adjustable from 0.8 leading to 0.8 lagging)
Max. Total Harmonic Distortion <3% <3% <3% <3% <3%
Maximum Output Overcurrent
Protection (A)
42 42 42 42 50
Eciency
Max. Eciency 97.8% 97.8% 97.8% 97.8% 97.8%
European Eciency 97.5% 97.5% 97.5% 97.5% 97.5%
Protection
PV String Current Monitoring Integrated
PV Insulation Resistance
Detection
Integrated
Residual Current Monitoring Integrated
PV Reverse Polarity Protection Integrated
Anti-islanding Protection Integrated
AC Overcurrent Protection Integrated
AC Short Circuit Protection Integrated
AC Overvoltage Protection Integrated
DC Switch Optional
DC Surge Protection Type III(Type II Optional)
AC Surge Protection Type III
AFCI Optional
Emergency Power O Optional
Remote Shutdown Optional
General Data
Operating Temperature Range
(℃)
-25 - +60
Relative Humidity 0 - 100%
Max. Operating Altitude (m)
*5
4000
Cooling Method Natural Convection

Other manuals for Goodwe GW3600D-NS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Goodwe GW3600D-NS and is the answer not in the manual?

Goodwe GW3600D-NS Specifications

General IconGeneral
BrandGoodwe
ModelGW3600D-NS
CategoryInverter
LanguageEnglish

Related product manuals