16 GOSSEN METRAWATT GMBH
Parameters Configuration
X1 = lower range limit, X2 = upper range limit,
MBU = X2 – X1
. These values refer to the configured sensor type
(see Configuration page 25), not to the C Designation.
Parameter Display Range Default Comment
Upper limit value for relay A1
oFF, 1 ... MBU
oFF, X1 ... X2
oFF / *
oFF / *
Relative (= default config.)
Absolute
Lower limit value for relay A1
Upper limit value for relay A2
Lower limit value for relay A2
Setpoint 2 SP L ... SP H X1
Ramp for rising setpoints oFF, 1 ... MBU pro min oFF
Ramp for falling setpoints oFF, 1 ... MBU pro min oFF
Heating current setpoint
(see Balancing)
Auto, oFF, 0.1 ... A H oFF
Not with step-action
controllers
1)
Proportional band heating 0.1 ... 999.9 % 10.0 / *
Proportional band cooling 0.1 ... 999.9 % 10.0 / * Only with 3-step controllers
2)
Dead band 0 ... MBU 0 Not with 2-step controllers
3)
Path delay time 0 ... 9999 s 100 / *
Read-out cycle time 0.5 ... 600.0 s 10.0 / *
Motor run-time
5 ... 5000 s 60
Only with step-action
controllers
4)
Switching hysteresis
0 ... 1,5%MBU 0,5%MBU / *
For limit value monitoring and
limit transducers
Maximum setpoint SP L ... X2 X2 / *
Minimum setpoint X1 ... SP H X1 / *
Maximum PWR –100 ... 100 % 100
Actual value correction
(see Balancing)
(Auto), –MBU/4 ... +MBU / 4 0 / *
Only with designations
C01 ... C24