6 GOSSEN METRAWATT GMBH
Identification of Controller R2100
Features C23 and E5 of controller GTR0210 cannot be
replaced.
Auxiliary voltage is generally AC 110 … 230 V.
A switch to deactivate the control outputs and a
switching facility for the display is always available
(see features F1 and F2 of controller GTR0210).
Feature
Designation
Electronic PDPI controller R2100
Controller types
2-step controller A1
3-step controller A2
Time response
medium XB0
short XB1
long XB2
Measuring range
Thermocouple type L Fe-CuNi 0 … 400 °CC01
0 … 800 °CC02
type J Fe-CuNi 0 … 400 °CC03
type K NiCr-Ni 0 … 400 °CC05
0 … 600 °CC06
0 … 800 °CC07
0 … 1200 °CC08
type R Pt13Rh-Pt 0 … 1600 °CC09
type S Pt10Rh-Pt 0 … 1600 °CC10
Resistance thermometer Pt100 0 … 100 °CC20
0 … 200 °CC21
0 … 400 °CC22
–100 … +200 °CC24
Direct current 0 … 5 mA C30
0 … 20 mA C31
0 … 20 mA, display 0.00 … 2.00 C32
Output type 1
st
switching point
Relay D1
Transistor D2
Limit contact
none G0
MIN / MAX G1
Rupture protection
direct action XH0
reverse action XH1