GOSSEN METRAWATT GMBH 31
Technical Data
For complete technical data refer to the following data sheets:
Controller R2080: Order no. 3-349-216-03
Controller R2100: Order no. 3-349-217-03
Controller R2180: Order no. 3-349-218-03
Annual mean relative humidity, no condensation 75%
Ambient temperature
Nominal range of use
Operating range
Storage range
0 °C ... + 50 °C
0 °C ... + 50 °C
–25 °C ... + 70 °C
Aux. Voltage Nominal Ranges of Use Power Consumption
Nominal Value Voltage Frequency
AC 110 V /
AC 230 V
AC 95 V ... 253 V 48 Hz ... 62 Hz
Max. 10 VA
typically 6 W
Relay Output Floating, normally open contact
Switching capacity AC/DC 250 V, 2 A, 500 VA / 50 W
Service life > 2•10
5
switching cycles at nominal load
Interference suppression Utilize external RC element (100 Ω - 47 nF)
at contactor
Transistor output suitable for commercially available semiconductor relays
(SSR)
Switching Status Open-Circuit Voltage Output Current
Active (load ≤ 800 Ω) < DC 17 V 10 ... 15 mA
Inactive < DC 17 V < 0.02 mA
Overload limit Short-circuit, continuous interruption
Electrical Safety
Safety class II, panel-mount device, DIN EN 61010-1 section 6.50.4
Fouling factor 1, per DIN EN 61010-1 section 3.7.3.1 and/or IEC 664
Overvoltage category II, per DIN EN 61010 appendix J and/or IEC 664
Operating voltage 300 V per DIN EN 61010
EMC requirements IEC/EN 61326