Heating Current Monitoring
Function Heating current is acquired with an external transformer (e.g. GTZ 4121).
An alarm is triggered if the current setpoint is fallen short of by more than 20% with
activated heat (control output I active), or if current is not “off” when the heat is switched
off. The alarm is not triggered until heating current is high enough when output I is active,
or when current drops to zero when output I is inactive.
Monitoring is inactive if the controller is switched to oFF, as well as in the case of step-
action controllers.
AMPS current
setpoint Heater phase nominal current is entered for this parameter. AMPS can be set to Auto for
automatic adjustment with the heater switched on. The currently measured value is
saved to memory.
Heating Circuit Monitoring
Function Can be set to active or inactive with the “Alarm 1” configuration digit (see
“Configuration” ).
Without external transformer, without additional parameters
Requires correct optimization of tu and Pb 1 control parameters,
i.e. heating circuit monitoring must be activated before self-tuning is started.
In the event of manual optimization or subsequent adaptation of control parameters,
the lower limit value for the tu parameter must be observed:
Pb 1 MRS
minimum tu =
50% ∆ϑ
Dt
∆ϑ
Dt = maximum temperature rise during actuation
Error message LE appears after approximately 2 times tu, if heat remains on at 100%
and measured temperature rise is too small.
Monitoring is not active:
where controller sort = limit transducer, actuator or step-action controller
during self-tuning
with standard signal input (R2100 C30, C31)
where PWR limiting YH < 20%