EasyManua.ls Logo

Gossen MetraWatt R2080 - Manual Operation with Binary Input; PWR out Offset with Binary Input

Gossen MetraWatt R2080
32 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GOSSEN METRAWATT GMBH 29
Manual Operation with Binary Input
Switching to manual operation is possible via the binary input.
Bumpless switching to manual operation with all controller sorts
The last PWR is “frozen” for step-action controllers as well.
The last switching status is retained for limit transducers.
Operation and display are identical to automatic operation, except that the LED lights up and the PWR
can be changed in the PWR display with the and keys.
When configured as a step-action controller (controller sort set to 2 through 5), the Y St parameter must be
set to 0.
The “alarm 2” configuration digit must be set to a value of 8 ... F to this end (compare CnF2 on page 27)
PWR Out Offset with Binary Input
When configured as a step-action controller (controller sort set to 2 through 5), control quality can be
significantly improved by means of PWR out offset where abrupt load fluctuations prevail.
When the contact at the binary input is closed, the controller’s PWR is increased by an amount equaling
YSt.
It is reduced by the same value when the contact is opened.
No function during self-tuning
–Where Y St = 0, the binary input activates manual operation (see above).
The “alarm 2” configuration digit must be set to a value of 8 ... F to this end (see also CnF2 on page 27).
Example:
If a machine requires an average of 70% heating power during production operation, but only 10% during idle
time, the difference of Y ST is set to 60%, and the binary input is only activated during production.

Related product manuals