Off / manual mode
I
II
A1
I
II
A1
W2
Actual value
Off
OPERATING LEVEL SWITCHING CONTROLLER
W2
Reg. ratio
Actual value
Manual mode
OPERATING LEVEL CONTINUOUS AND STEP CONTROLLER
Alarm function and error signalling same as with automatic mode.
The positioning outputs are not controlled by the controller function but by the
rotary knob.
Manual/automatic switch-over is bumpless in both directions.
Continuous controller: The regulation ratio is shown in %. Changes in value are
slow in the spring ranges of the rotary knob and are
instantly passed to the control outputs.
Step controller: The switching output I (more) / II (less) is directly control-
led by turning the knob to the right/left into the spring
range. With position readback available (marking A4), the
measured position is shown in % while lines are shown
with marking A2, A3.
A2
A2
No alarm function
No error signalling
The positioning outputs are inactive with the rotary knob not actuated.
The switching output I ("heat") / II ("cool") is directly controlled by
turning the knob to the right / left into the spring range