GOSSEN-METRAWATT GMBH 31
Self-optimizing
Procedure
The actual set point at the start remains valid; it can no longer be changed (slave controller: a changing external set point is only displayed)
Activation/deactivation of the second set point does not
become effective
Set set point ramps are not considered
Overshooting cannot be avoided when starting in the working point (actual value corresponds nearly to set point)a
Stop
Optimizing can be stopped at any time with (
automatic mode) and/or by switching over to manual / Off with
Should an error occur while optimizing, the controller no longer issues a positioning signal. Optimizing must be stopped.
More information about error messages on request.
Self-optimizing is enabled when supplied (default setting K0). Disabling via DIP switch:
Self-optimizing serves to determine optimum control dynamics that is, the parameters Pb I, Pb II, tu and tc are
determined.
Getting started
Complete configuration must be made before
self-optimizing is started
The set point must be set to the value required after
optimizing.
Start
Self-optimizing is started when both keys on the operating level (automatic or manual/Off mode) are briefly
pressed simultaneously. It cannot be started with the controller types "Positioner" or "Limit monitor"
tun1...tun8 is flashingly shown on all operating levels during the optimizing run
When optimizing is successfully ended, the controller enters automatic mode.
With a three-state controller (controller type = 4 and 5), cooling is activated when the high limit responds in order to prevent overheating.
Self-optimizing then performs an oscillation test around the set point.
I
II
A1
W2
Actual
I
II
A1
W2
Actual
Actual
Start
Stop
Slow flashing
or
A2
A2
12345