GOSSEN-METRAWATT GMBH 24
Differential controller
See page 28 for Parameters
The actual value difference = 1st actual value 2nd actual value is controlled to the set differential set point.
The differential set point can be set on the range
± range span.
Limit monitoring is referred to the difference in actual values and not the two actual values.
If an attempt is made to adjust the differential set point on the operating level, display mode 1st actual value / 2nd actual value, by means of the
potentiometer, no is briefly shown on the lower display.
Slave controller
See page 28 for Parameters
The external set point applied to the 2nd signal input replaces the internal set point.
The set point ramp function (see page 36) is maintained.
When switching over to the second set point by means of a binary input, the controller becomes a fixed value controller with the set point SP 2.
The lower and upper limit of the external set point is scaled by means of the parameters rn L and rn H (2nd standard signal for B4 and B5).
The parameters SP L and SP H limit the external set point for control and display.
If an attempt is made to adjust the set point on the operating level, display mode actual value / set point, by means of the potentiometer, no is briefly
shown on the lower display.