Limit monitor
Start-up suppression: the alarm suppression at start-up is active (configuration digit "Alarms 1") until the temperature has exceeded the low limit for
the first time. When cooling, the suppression is effective until the high limit has been fallen below for the first time. It is effective when: The auxiliary
voltage is switched on, the actual set point is changed and the second set point is activated, as well as when changing from Off to automatic mode.
Alarm relay n NOC
Alarm relay n NCC
n = 1, 2
ALnL ALnH
Limits relative
ALnL ALnH
Limits absolute
Actual valueSet point
Hysteresis (HYSt)