GOSSEN-METRAWATT GMBH 6
Identifying the unit
Electronic controller with self-optimizing facility, second set point, 2 limit relays, front dimensions 48 x 96 mm (W x H) R2600
Electronic controller with self-optimizing facility, second set point, 2 limit relays, front dimensions 96 x 48 mm (W x H) R2601
Controller type
Two-state controller with heating current monitor 1 relay and 1 transistorized output
Three-state controller with heating current monitor / step controller 2 relay and 2 transistorized outputs
Contin. controller / three-state with heating curr. monitor / step controller 1 continuous, 2 transistorized and 2 relay outputs
Step controller with position read-back / three-state controller 2 relay and 2 transistorized outputs
A1
A2
A3
A4
Measuring ranges
Signal input Thermocouple, configurable Type J, L –18 ... 850 °C / 0 ... 1562 °F
Type K –18 ... 1200
°C / 0 ... 2192 °F
Type S, R –18 ... 1770
°C / 0 ... 3218 °F
Type B 0 ... 1820
°C / 32 ... 3308 °F (espec. from 600 °C)
Type N –18 ... 1300
°C / 0 ... 2372 °F
Resistance thermometer Pt 100 – 100 ... 500
°C / –148 ... 932 °F
B1
Signal input Standard signal, configurable 0 / 2 ... 10 V or 0 / 4 ... 20 mA B2
Both signal inputs are commonly configurable same as B1 for differential controller B3
1st signal input configurable same as B1 and 2nd signal input same as B2 for slave controller B4
Both signal inputs configurable same as B2 for differential controller / slave controller B5
Auxiliary voltage AC 230 V
AC 110 V
AC 24V
DC 24 V
C1
C2
C3
C4
C1 → C2 or C2 → C1 internal plug-change possible