GOSSEN-METRAWATT GMBH 37
Heating circuit monitor
Function Active / inactive configurable with the configuration digit "Alarms" (see Configuration)
Without external transformer, without additional parameters
Correct optimization of the control parameters tu and Pb I is a pre-condition!
i.e. before self-optimization is started, heating circuit monitoring must be activated.
The lower limit for the tu parameter must be maintained for manual optimization or subsequent adjustment of the control
parameters:
Pb I MBU
minimum tu =
50%
∆ϑ t
∆ϑ t = maximum temperature rise during start-up
The error message LE is generated after approximately 2 times tu if the heater remains switched on 100 % and
the increase in temperature is too small
The monitor is inactive, when
Controller type = limit monitor, positioner or step controller
During self-optimizing
With standard signal input (marking B2)
The limitation of the regulation ratio Y H < 20 %