Alarm Troubleshooting
88 312776K
E-9: Not used
E-10: REMOTE STOP ALARM
Cause Solution
Automation has requested that the system abort all oper-
ations.
Abort operations. Troubleshoot automation system.
E-11: PURGE VOLUME ALARM
Cause Solution
ProMix 2KS solvent flow switch is not activated while
purging.
Verify that the gun is not shut off and that the solvent
flow switch is activated while purge is taking place.
Minimum flush volume is not achieved. Increase solvent supply or decrease minimum volume
setting.
No meter pulses during Color/Catalyst Dump. Color change solvent supply not set up or functional.
Check Color Change setup.
Table 11. Alarm Troubleshooting