GREE Photovoltaic Direct-driven Inverter Multi VRF Units
171
Troubleshooting:
2.3.4.22 “b6” Malfunction of inlet tube temperature sensor of vapor liquid separator
Error display:
ODU mainboard, IDU wired controller and IDU receive light board will display
Error judgment condition and method:
Sample the AD value of temperature sensor through temperature sensor detecting circuit and judge
the range of AD value; if the sampled AD value exceeds upper limit and lower limit in 30 seconds
continuously, report the error.
Possible reason
■Poor contact between temperature sensor and terminal in mainboard interface
■Temperature sensor is abnormal
■Detecting circuit is abnormal