GREE Photovoltaic Direct-driven Inverter Multi VRF Units
14
5 ELECTRICAL PARAMETERS
Outdoor Unit (208V)
Outdoor units
Power Supply Fuse Capacity
Minimum Circuit
Ampacity
Maximum Overcurrent
Protection
V/ Ph /Hz A A A
GMV-Y72WM/C-F(U)
208V 3~ 60Hz 45 35.3 45
GMV-Y96WM/C-F(U)
208V 3~ 60Hz 45 43.6 45
GMV-Y120WM/C-F(U)
208V 3~ 60Hz 45 44.8 45
GMV-Y144WM/C-F(U)
208V 3~ 60Hz 45+45 35.3+35.3 45+45
GMV-Y168WM/C-F(U)
208V 3~ 60Hz 45+45 35.3+43.6 45+45
GMV-Y192WM/C-F(U)
208V 3~ 60Hz 45+45 43.6+43.6 45+45
GMV-Y216WM/C-F(U)
208V 3~ 60Hz 45+45 43.6+44.8 45+45
GMV-Y240WM/C-F(U)
208V 3~ 60Hz 45+45 44.8+44.8 45+45
GMV-Y264WM/C-F(U)
208V 3~ 60Hz 45+45+45 35.3+43.6+43.6 45+45+45
GMV-Y288WM/C-F(U)
208V 3~ 60Hz 45+45+45 43.6+43.6+43.6 45+45+45
GMV-Y312WM/C-F(U)
208V 3~ 60Hz 45+45+45 43.6+43.6+44.8 45+45+45
GMV-Y336WM/C-F(U)
208V 3~ 60Hz 45+45+45 43.6+44.8+44.8 45+45+45
GMV-Y360WM/C-F(U) 208V 3~ 60Hz 45+45+45 44.8+44.8+44.8 45+45+45
Outdoor Unit (240V)
Outdoor units
Power Supply Fuse Capacity
Minimum Circuit
Ampacity
Maximum Overcurrent
Protection
V/ Ph /Hz A A A
GMV-Y72WM/C-F(U)
240V 3~ 60Hz 40 30.3 40
GMV-Y96WM/C-F(U)
240V 3~ 60Hz 40 37.3 40
GMV-Y120WM/C-F(U)
240V 3~ 60Hz 40 39.8 40
GMV-Y144WM/C-F(U)
240V 3~ 60Hz 40+40 30.3+30.3 40+40
GMV-Y168WM/C-F(U)
240V 3~ 60Hz 40+40 30.3+37.3 40+40
GMV-Y192WM/C-F(U)
240V 3~ 60Hz 40+40 37.3+37.3 40+40
GMV-Y216WM/C-F(U)
240V 3~ 60Hz 40+40 37.3+39.8 40+40
GMV-Y240WM/C-F(U)
240V 3~ 60Hz 40+40 39.8+39.8 40+40
GMV-Y264WM/C-F(U)
240V 3~ 60Hz 40+40+40 30.3+37.3+37.3 40+40+40
GMV-Y288WM/C-F(U)
240V 3~ 60Hz 40+40+40 37.3+37.3+37.3 40+40+40
GMV-Y312WM/C-F(U)
240V 3~ 60Hz 40+40+40 37.3+37.3+39.8 40+40+40
GMV-Y336WM/C-F(U)
240V 3~ 60Hz 40+40+40 37.3+39.8+39.8 40+40+40
GMV-Y360WM/C-F(U) 240V 3~ 60Hz 40+40+40 39.8+39.8+39.8 40+40+40
Power cable wire gauge and circuit breaker must be selected based on the above parameters
and in compliance with local safety requirements. If there is conflict between above parameters and
national requirements, please contact the manufacture promptly.
If power cable wire gauge and circuit breaker is out of the above design range, fire hazard may