GREE Photovoltaic Direct-driven Inverter Multi VRF Units
179
Troubleshooting:
2.3.4.30 “C4” IDU missing error
Error display:
ODU mainboard, IDU wired controller and IDU receive light board will
display
Error judgment condition and method:
If ODU hasn’t received inverter fan drive board data in continuous 30s, report the error.
Possible reason
■Communication wire is in poor connection
■Power supply of IDU is cut off
■IDU mainboard is abnormal