GREE Photovoltaic Direct-driven Inverter Multi VRF Units
220
Troubleshooting:
2.3.4.82 “H8” Fan drive IPM high temperature protection
Error display:
ODU mainboard will display
Error judgment condition and method:
Check the error code on nixie tube of ODU main control board. If H8 is displayed, it indicates fan
drive IPM high temperature protection
Possible reason
■Thermal grease of IPM module hasnt been spread or thermal grease is not spread evenly or
thermal grease is dry;
■Screw of IPM module is not tightened;
■Fan drive board is abnormal
Troubleshooting: