GREE Photovoltaic Direct-driven Inverter Multi VRF Units
231
2.3.4.95 “J7” Gas-mixing protection of 4-way valve
Error display:
ODU mainboard, IDU wired controller and IDU receive light board will display
Error judgment condition and method:
Check the system high pressure and low pressure
through pressure sensor. When the difference between system high pressure and low pressure is lower
than 0.1MPa after starting operation, the unit will stop for protection.
Possible reason
■Coil or connection wire is abnormal;
■Mainboard is abnormal;
■Internal part of 4-way valve is abnormal;
Troubleshooting: