EasyManua.ls Logo

Gree ME30-24/E5 - DI;Do

Gree ME30-24/E5
26 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Modbus Gateway(Pro) Technical Service Manual
17
RS485-2
TX
This device does not use this LED indicator.
Power
When power supply of Modbus Gateway(Pro) is normal, it
will be always on..
Run
When Modbus Gateway(Pro) works normally, it will blink.
Alarm
This device doesnt use this LED indicator.
1.3 DI/DO
This gateway supports 5 DIs(digital inputs) and 5 DOs(digital outputs); DO6 is reserved.
DI1...DI5
Digital inputs: 0/1 digital signals(binary system), applicable for those with power supply
DI1: in CAN2 network, fire alarm signal, connect 1 to the power of 12V, input fire alarm
signal 1 in DI 1 port, then Modbus gateway(Pro) will give out control, all units stop
operation immediately;disconnect 1 or connect to 0, input signal 0 in DI 1
port,resume operation of all ODUs.
In CAN1 network, fire alarm signal, connect 1 to the power of 12V, input fire alarm
signal 1 in DI 1 port, then Modbus gateway(Pro) will give out control, all units stop
operation immediately;disconnect 1 or connect to 0, input signal 0 in DI 1
port,resume operation of IDUs manually.
DI2...DI5: Defined by the user.
DO1...DO5 digital outputs: Relay output, normally-open contact
Max admissible power: 250VAC, 3A; 30VDC, 3A
Example: write 1 into DO5 of Modbus protocol and the two contacts of DO5 relay will be
closed; write 0 into DO5 of Modbus protocol and the two contacts of DO5 relay will
be cut off.

Other manuals for Gree ME30-24/E5

Related product manuals