Wired Controller XK46
8
Panel of wired
controller
Self-tapping Screw ST3.9X25
MA
Soleplate of wired
controller
3.1 INSTALLATION OF WIRED CONTROLLER
3.1.1 Communication Line Selection
Fig. 3.2 Length of communication line
Total length of
communication line
between indoor unit
and wired controller
L (m/feet)
Polyvinyl
chloride
sheathed
cord.
(60227 IEC 52
/60227 IEC
53)
1.25 mm
2
(2×AWG1
8~2×AWG
16)
(1)Total length of
communication line can't
exceed 250m (820-1/5feet).
(2)The cord shall be Circular
cord (the cores shall be
twisted together).
(3)If unit is installed in
places with intense
magnetic field or strong
interference, it is necessary
to use shielded wire.