Wired Controller XK46
20
Paramet
er
code
Parameter
name
Parameter
range
Viewing method
C18
One-button
viewing of indoor
unit project
number
1-255:Project
Number of
online indoor
unit
Operation method:
Enter viewing, short-press “MODE” button in
“C18” status to turn on the function of
one-button viewing indoor unit project code, and
the wired controller will enter the interface of
viewing indoor unit project code. Press “ ” or
button to select the indoor unit.
Display method:
Temperature zone: displays number of the
current indoor unit
Timer zone: displays project number of indoor
unit
Note:
1) After turning on the one-button viewing
function, each wired controller of the entire
system will display the project number of its
controlling indoor unit on its timer zone. (The
timer zone will display different project numbers
in turn with an interval of 3 seconds if one wired
controller is controlling multiple indoor units.)
2) Slave wired controller cannot view “C18”.
Cancel method:
1) If user exits the “C18” interface manually, the
one-button viewing function will be immediately
turned off.
2) If system exits the “C18” interface due to no
action in 20 seconds, user has to press the
“ON/OFF” button under on/off status to cancel
this function.
3) After the one-button viewing function is
turned on, pressing the “ON/OFF” button of any
wired controller of the same system network
under on/off status will cancel this function.
Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.