Wired Controller XK46
23
Parame
ter
code
Parameter name
Parameter
range
Defa
ult
valu
e
Note
P13
Set address of wired
controller
01: master wired
controller
02: slave wired
controller
01
When two wired controllers control
one indoor unit (or several indoor
units), the addresses of the two wired
controllers should be different.
Assistant wired controller (02) is
without unit parameter setting
function except setting its address.
P14
Set quantity of group
control indoor units
00: forbid this
function
01-16: indoor
unit quantity
01
Set the corresponding value
according to the connected indoor
unit quantity.
P16
Set unit of
temperature
00:Celsius
01:Fahrenheit
00
--
P30
Set static pressure
of indoor fan motor
01-09: static
pressure level of
indoor fan motor
05
There are two kinds of static pressure
level:
5 levels: 03, 04, 05, 06, 07
9 levels: 01, 02, 03, 04, 05, 06, 07,
08, 09
Wired controller can be adapted
to the different types of indoor units
that it possesses 1-9 level selection
for setting static pressure. When the
indoor unit with 5 static pressure
levels received the level setting sent
by wired controller is less than 3, it
will be settled as the 3rd level; if it is
over 7, it will be settled as the 7th
level.