Microprocessor Controller for DOAS 43
®
Supply_Duct_Static_
Pressure_Setpoint
Supply Duct Static Pressure
Setpoint
38 AV
ReadCOV_
Commandable
0.1 40075 Holding 2
Space_CO2_Setpoint Space CO2 Setpoint 39 AV
ReadCOV_
Commandable
0.1 40077 Holding 2
SF_Control_Signal_
BMS
BMS to control signal for
supply fan speed
133 AV
ReadCOV_
Commandable
0.1 40083 Holding 2
EF_Control_Signal_
BMS
BMS to control signal for
exhaust fan speed
134 AV
ReadCOV_
Commandable
0.1 40085 Holding 2
OAD_Control_Signal_
BMS
Allows the BMS to control
OAD position. True = BMS.
False = Local.
136 AV
ReadCOV_
Commandable
0.1 40089 Holding 2
Outside_Air_Damper_
Minimum_Setpoint
Outside Air Damper
Minimum Setpoint
137 AV
ReadCOV_
Commandable
1 40091 Holding 2
Aux_BMS_Analog_
Output_1
BMS Commanded auxilary
analog output
138 AV
ReadCOV_
Commandable
0.1 40093 Holding 2
Aux_BMS_Analog_
Output_2
BMS Commanded auxilary
analog output
139 AV
ReadCOV_
Commandable
0.1 40095 Holding 2
Aux_BMS_Analog_
Output_3
BMS Commanded auxilary
analog output
140 AV
ReadCOV_
Commandable
0.1 40097 Holding 2
Aux_BMS_Analog_
Output_4
BMS Commanded auxilary
analog output
141 AV
ReadCOV_
Commandable
0.1 40099 Holding 2
Appendix: Points List
VARIABLE DESCRIPTION
ACTIVE
TEXT
INACTIVE
TEXT
BACNET MODBUS
OBJECT
INSTANCE
OBJECT
TYPE
ACCESS HYST INDEX
REGISTER
TYPE
SIZE