EasyManua.ls Logo

Greenheck Microprocessor Controller - Page 43

Greenheck Microprocessor Controller
56 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Microprocessor Controller for DOAS 43
®
Supply_Duct_Static_
Pressure_Setpoint
Supply Duct Static Pressure
Setpoint
38 AV
ReadCOV_
Commandable
0.1 40075 Holding 2
Space_CO2_Setpoint Space CO2 Setpoint 39 AV
ReadCOV_
Commandable
0.1 40077 Holding 2
SF_Control_Signal_
BMS
BMS to control signal for
supply fan speed
133 AV
ReadCOV_
Commandable
0.1 40083 Holding 2
EF_Control_Signal_
BMS
BMS to control signal for
exhaust fan speed
134 AV
ReadCOV_
Commandable
0.1 40085 Holding 2
OAD_Control_Signal_
BMS
Allows the BMS to control
OAD position. True = BMS.
False = Local.
136 AV
ReadCOV_
Commandable
0.1 40089 Holding 2
Outside_Air_Damper_
Minimum_Setpoint
Outside Air Damper
Minimum Setpoint
137 AV
ReadCOV_
Commandable
1 40091 Holding 2
Aux_BMS_Analog_
Output_1
BMS Commanded auxilary
analog output
138 AV
ReadCOV_
Commandable
0.1 40093 Holding 2
Aux_BMS_Analog_
Output_2
BMS Commanded auxilary
analog output
139 AV
ReadCOV_
Commandable
0.1 40095 Holding 2
Aux_BMS_Analog_
Output_3
BMS Commanded auxilary
analog output
140 AV
ReadCOV_
Commandable
0.1 40097 Holding 2
Aux_BMS_Analog_
Output_4
BMS Commanded auxilary
analog output
141 AV
ReadCOV_
Commandable
0.1 40099 Holding 2
Appendix: Points List
VARIABLE DESCRIPTION
ACTIVE
TEXT
INACTIVE
TEXT
BACNET MODBUS
OBJECT
INSTANCE
OBJECT
TYPE
ACCESS HYST INDEX
REGISTER
TYPE
SIZE