20
05
Battery type
AGM (Default)
Flood
User-Defined
If “User-Defined” is selected, battery charge voltage and low DC cut-
off voltage can be set up in program 19, 20 and 21.
User-Defined 2
(Suitable for lithium battery when no communicating with BMS)
If “User-Defined 2” is selected, battery charge voltage and low DC cut-
off voltage can be set up in program 19, 20 and 21. It is recommended
to set to the same voltage in program 19 and 20(full charging voltage
point of lithium battery). The inverter will stop charging when the
battery voltage reaches this setting.
Lithium (Only suitable when communicate with BMS)
06
Auto restart when
overload occurs
Restart disable (default)
Restart enable
Restart bypass
When overload under battery modesystem will switch to bypass
automatically
08
Output voltage
240Vdefault
230V
220V
208V