EasyManuals Logo

Growatt SPF 3000TL LVM User Manual

Growatt SPF 3000TL LVM
47 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #12 background imageLoading...
Page #12 background image
10
5.
Make sure the wires are securely connected.
PV Connection
CAUTION: Before connecting to PV modules, please install separately a DC circuit breaker between inverter
and PV modules.
WARNING! All wiring must be performed by a qualified personnel.
WARNING! It'’ very important for system safety and efficient operation to use appropriate cable for PV module
connection. To reduce risk of injury, please use the proper recommended cable size as below.
Model
Typical Amperage
Cable Size
Torque
SPF 3000TL LVM
80A
6 AWG
1.4~1.6 Nm
PV Module Selection:
When selecting proper PV modules, please be sure to consider below parameters:
1.
Open circuit Voltage (Voc) of PV modules not exceeds max. PV array open circuit voltage of inverter.
2.
Open circuit Voltage (Voc) of PV modules should be higher than min. battery voltage.
Solar Charging Mode
INVERTER MODEL
SPF 3000TL LVM-24P
SPF 3000TL LVM-48P
Max. PV Array Open Circuit Voltage
145Vdc
145Vdc
PV Array MPPT Voltage Range
30~115Vdc
60~115Vdc
Min. battery voltage for PV charge
17Vdc
34Vdc
Please follow below steps to implement PV module connection:
1.
Remove insulation sleeve 10 mm for positive and negative conductors.
2.
Check correct polarity of connection cable from PV modules and PV input
connectors. Then, connect positive pole (+) of connection cable to positive
pole (+) of PV input connector. Connect negative pole (-) of connection
cable to negative pole (-) of PV input connector.
3.
Make sure the wires are securely connected.
CAUTION: Appliances such as air conditioner are required at least 2~3 minutes to restart because it’s
required to have enough time to balance refrigerant gas inside of circuits. If a power shortage occurs and
recovers in a short time, it will cause damage to your connected appliances. To prevent this kind of damage,
please check with manufacturer of air conditioner that if it’s equipped with time-delay function before
installation. Otherwise, this off grid solar inverter will trig overload fault and cut off output to protect your
appliance but sometimes it still causes internal damage to the air conditioner.
CAUTION: Important
Be sure to connect AC wires with correct polarity. If L and N wires are connected reversely, it may cause
utility short-circuited when these inverters are worked in parallel operation.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Growatt SPF 3000TL LVM and is the answer not in the manual?

Growatt SPF 3000TL LVM Specifications

General IconGeneral
ModelSPF 3000TL LVM
Rated Power3000W
Input Voltage230 VAC
Output Voltage230 VAC
Battery Voltage24 VDC
Max PV Input Voltage145VDC
Max Charging Current80A
Peak Efficiency93%
Output Frequency50 Hz/60 Hz
Dimensions330 x 485 x 135 mm
Battery TypeLead-acid or Lithium
CommunicationRS232
MPPT Voltage Range30-115VDC

Related product manuals