7.7 Alarms and warnings
In the WarningCode module, the cause of a booster system
warning can be read. A warning has no influence on the booster
system operation.
In the FaultCode module, the cause of a booster system alarm
can be read. A booster system alarm always leads to a reaction in
the booster system operation, usually all pumps are stopped, but
some Hydro MPC or Control MPC alarms have programmable
alarm action types.
The complete list of possible alarm and warning codes is shown
below.
1)
For Hydro/Control MPC and Multi-E model H and later, it can
be automatic (A) or selectable Automatic/Manual (A/M).
2)
For Hydro/Control MPC and Multi-E model H and later, it can
be none or programmable (Prog.).
Event action programmable are Stop, Stop with delay, Min.,
UserDef, Max., Pumps in local, Emergency run.
The Hydro Multi-E model G is always stopped in case of an
alarm.
Module Name Description
3 WarningCode Code for booster system warning.
4 FaultCode Code for booster system alarm.
Code Alarm/warning description Reset type
1)
Action type
2)
3 External fault signal A/M Prog.
10 Communication fault, pump A None
80 Hardware fault, IO 351 pump module A None
80 Hardware fault, IO 351 I/O module A None
83 Verification error, EEPROM parameter area A None
88 Sensor fault, general measuring sensor A None
89 Signal fault, closed-loop feedback sensor A/M Prog.
91 Temperature sensor 1 signal fault A/M Prog.
157 Real Time Clock error A None
161 Sensor supply fault, 5 V A None
162 Sensor supply fault, 24 V A None
165 Signal fault, analog input A1 A/M Prog.
166 Signal fault, analog input A2 A/M Prog.
167 Signal fault, analog input A3 A/M Prog.
175 Temperature sensor 2 signal fault A/M Prog.
190 Limit exceeded, supervised item 1 A/M Prog.
191 Limit exceeded, supervised item 2 A/M Prog.
203 Alarm on all pumps A/M Prog.
204 Inconsistency between sensors A None
208 Operation outside performance range A/M Prog.
210 High pressure A/M Prog.
211 Low pressure A/M Prog.
213 VFD not ready A None
214 Water shortage A/M Prog.
215 Soft pressure buildup timeout A/M Prog.
216 Pilot pump alarm A None
219 Pressure relief not adequate A None
231 Ethernet: No IP address from DHCP server A None
232 Ethernet: Auto-disabled due to misuse A None
248 Fault, battery/UPS A None
From device
Pump alarms. See section 7.9 Zone pump modules (ZonePumpModule,
modules 29 to 34).
- None