4. Specifications
4.1 CIM module
4.2 CIM 150 PROFIBUS DP
The table below provides an overview of the specifications for
Grundfos CIM 150 and CIU 150. For further details, please refer
to the specific sections of this functional profile.
4.3 CIM 500 PROFINET IO
The table below provides an overview of the specifications for
Grundfos CIM/CIU 500 ethernet for PROFINET IO. For further
details, please refer to the specific sections of this functional
profile.
General data Description Comments
Ambient humidity 30-95 % Relative, non-condensing.
Operating temperature -20 to +45 °C
Storage temperature -25 to +70 °C
GENIbus visual diagnostics LED2
Will be in one of these states:
Off, permanently green, flashing red, permanently
red.
See section 5.6 Status LEDs for PROFIBUS DP
and section 6.5 Status LEDs for PROFINET IO.
Power supply (CIU) 24-240 V Located in the CIU.
GENIbus connection type (CIU) RS-485, 3-wire + screen Conductors: A, B and Y.
CIU box enclosure class IP54
CIU box dimensions (H x W x D) 182 x 108 x 82 mm
PROFIBUS DP specifications Description Comments
PROFIBUS implementation class DP-V0 Intelligent pump profile.
PROFIBUS connector Screw-type terminal A, B, DGND, VP (+5 V).
PROFIBUS connection type RS-485, two-wire Conductors: A, B.
Maximum cable length 100 metres at 12 Mbits/s
Corresponds to 328 feet. See section 5.3.1 Data
transmission rates and cable length.
Slave address 1-126
Set via rotary switches SW3 and SW4.
See section 5.4 Setting the PROFIBUS address.
Line termination On or off
Set via DIP switches SW1 and SW2.
See section 5.5 Termination resistors.
Auto detected
Recommended cable cross-section 0.20 - 0.25 mm
2
AWG24 or AWG23
Supported transmission speed 9.6 Kbits/s to 12 Mbits/s Auto detected.
PROFIBUS visual diagnostics LED1
Off, permanently green, flashing red, permanently
red.
See section 5.6 Status LEDs.
Maximum number of PROFIBUS devices
at a physical network segment
32
Up to 125 devices if repeaters are used (physically
segmented network).
PROFINET IO specifications Description Comments
Application layer
DHCP, HTTP, Ping, FTP, SMTP, SNTP,
PROFINET IO
Rotary switch in position 0.
Transport layer TCP
Internet layer Internet protocol V4 (IPv4)
Link layer ARP, Media Access Control (ethernet)
Ethernet cable CAT5, CAT5e or CAT6
Supports auto cable-crossover detecting (Auto-
MDIX)
Maximum cable length 100 metres at 10/100 Mbits/s Corresponds to 328 feet.
Transmission speed 10 Mbits/s, 100 Mbits/s Auto-detected.
Industrial Ethernet protocols PROFINET IO, Modbus TCP
Selected with rotary switch, section 6.2 Setting the
Industrial Ethernet protocol.