7.8 Measurement modules
This is measurement data that can be read in Hydro MPC,
Control MPC and Hydro Multi-E.
PROFIBUS/PROFINET direction: Inputs.
Module Name
Data
type
Unit Description
MPC
Multi-E model G
Multi-E/TPED model H and later
MAGNA3-D
3 WarningCode 5 -
The Grundfos-specific warning code.
For a list of warning codes. See section 7.7 Alarms and
warnings.
● - ●●
4 FaultCode 5 -
The Grundfos-specific alarm code.
For a list of alarm codes. See section 7.7 Alarms and
warnings.
● ●●●
5 VolumeFlow 8 m
3
/h
Provides the flow through the system as estimated or
measured.
SSS●
6 Head 8 bar
Provides the differential pressure between inlet and outlet
as estimated, or measured, by the booster system.
SSS●
7 RemotePressure 8 bar
Provides the measured pressure at an external pressure
sensor. This pressure sensor must be installed for this
value to be valid.
S-SS
8 InletPressure 8 bar
Provides the inlet pressure if a pressure sensor is
configured and installed at the inlet.
It has an offset of -1.000 bar.
S-S-
9 OutletPressure 8 bar
Provides the outlet pressure measured by a pressure
sensor.
S-S-
10 Level 8 m
Provides the tank level.
Requires that a level sensor is installed.
It has an offset of -100 metres.
SSS-
11 FeedTankLevel 8 m
Provides the feed tank level.
Requires that a level sensor is installed.
It has an offset of -100 metres.
S-S-
12 Power 8 W
Provides the actual power consumed by the booster
system.
●** ●●●
13 Energy 8 Wh
Provides the accumulated electric energy consumption of
the system.
●** ●●●
14 RemoteTemperature 8 °C
Provides the temperature measured by a remote
temperature sensor.
SSS-
15 AmbientTemperature 8 °C
Provides the ambient temperature measured by a
temperature sensor.
S-S-
16 InletTemp 8 °C
Provides the inlet temperature measured by a temperature
sensor.
S---
17 OutletTemp 8 °C
Provides the outlet temperature measured by a
temperature sensor.
S---
18 TemperatureDifference 8 °C Provides the differential temperature. S - - -
19 OperationTime 8 h Provides the total operating hours of the booster system. ● ●●●
20 ActualSetpoint 8 %
Selected system control-loop setpoint.
See description of scaling for a setpoint in 7.2 Control
module (ControlModule, module 2)
● ●●●
21 RelativePerformance 8 %
Value of speed control signal to pumps that are not
stopped or running at maximum speed.
● ●●●