22 SystemActiveFunctions 6 Bits
Indicates active system functions.
0: -
1: Emergency run function
2: Standby pumps
3: Pump test run
4: Alternative setpoint
5: Clock program
6: Remote VNC (Virtual Network Connection)
7: Remote bus
8: Remote service port
9: Pressure-relief function
10: Soft-pressure function
11: Low-flow boost
12: Low-flow stop
13: Proportional pressure.
● ---
23 DigitalInput 5 Bits
Provides the status of the external digital inputs.
Logical "0": The input is 0 V.
Logical "1": The input is 5 V.
0: Digital input 1
1: Digital input 2
2: Digital input 3
3: Digital input 4
4: Digital input 5
5: Digital input 6
6: Digital input 7
7: Digital input 8.
● ●●●
24 DigitalOutput 5 Bits
Provides the status of the external digital outputs.
Logical "0": The output is 0 V.
Logical "1": The output is 5 V.
0: Digital output 1
1: Digital output 2
2-7: Reserved.
● ●●●
25 PumpsPresent 5 Bits
One bit for each pump configured in the system.
Logical "1": The pump is present.
0: Zone pump 1 present
1: Zone pump 2 present
2: Zone pump 3 present
3: Zone pump 4 present
4: Zone pump 5 present
5: Zone pump 6 present
6: Pilot pump present
7: Backup pump present.
● ●●●
26 PumpsRunning 5 Bits
One bit for each pump which is running.
Logical "1": The pump is running.
0: Zone pump 1 running
1: Zone pump 2 running
2: Zone pump 3 running
3: Zone pump 4 running
4: Zone pump 5 running
5: Zone pump 6 running
6: Pilot pump running
7: Backup pump running.
● ●●●
27 PumpsFault 5 Bits
One bit for each pump indicating if the pump is faulty.
Logical "1": The pump is faulty.
0: Zone pump 1 fault
1: Zone pump 2 fault
2: Zone pump 3 fault
3: Zone pump 4 fault
4: Zone pump 5 fault
5: Zone pump 6 fault
6: Pilot pump fault
7: Backup pump fault.
● ●●●
Module Name
Data
type
Unit Description
MPC
Multi-E model G
Multi-E/TPED model H and later
MAGNA3-D