S: Sensor required.
●: Always available.
●*: Hydro Multi-E model G only.
For Hydro/Control MPC, see the table below.
●**: MPC-E only.
●***: CU 352 only.
28 PumpsCommFault 5 Bits
One bit for each pump indicating that there is no
communication with the pump.
Logical "1": No communication with the pump.
0: Communication fault, zone pump 1
1: Communication fault, zone pump 2
2: Communication fault, zone pump 3
3: Communication fault, zone pump 4
4: Communication fault, zone pump 5
5: Communication fault, zone pump 6
6: Communication fault, pilot pump
7: Communication fault, backup pump.
● ●●●
41 UserSetpoint 8 %
User setpoint as written from the bus or selected on the
booster.
See description of scaling for a setpoint in 7.2 Control
module (ControlModule, module 2).
● - ●●
42 AnalogueInfluence 8 % Influence from analog input. ● - ●●
43 NoOfPowerOn 8 - Number of power-on cycles. ● ---
44 FeedBackSensorUnit 5 Enum
Scaling unit for the closed-loop feedback sensor
0: bar 7: m
3
/s 14: l/h
1: mbar 8: l/s 15: l/min
2: m 9: gpm 16: gal/h
3: kPa 10: °C 17: gal/s
4: psi 11: °F 18: ft
3
/h
5: ft 12: % 19: ft
3
/min
6: m
3
/h 13: m
3
/min 20: ft
3
/s
●*-●●
45 FeedbackSensorMin 6
Sensor
unit
Minimum value for the closed-loop feedback sensor. ● - ●●
46 FeedbackSensorMax 6
Sensor
unit
Maximum value for the closed-loop feedback sensor. ● - ●●
51 AutoModePumps 5 Bits
One bit for each pump indicating if the pump is
commanded to stop from PROFIBUS/PROFINET or is in
auto mode, controlled from CU 352.
Logical "1": Pump in auto mode.
0: Zone pump 1 in auto mode
1: Zone pump 2 in auto mode
2: Zone pump 3 in auto mode
3: Zone pump 4 in auto mode
4: Zone pump 5 in auto mode
5: Zone pump 6 in auto mode
6: Pilot pump in auto mode
7: Backup pump in auto mode.
The data module ControlPumps (module 50) is used to
command the individual pumps.
●***---
52 FlowMeasurement1 6 0.1 m
3
/h Flow measurement 1 from sensor. S - - -
53 FlowMeasurement2 6 0.1 m
3
/h Flow measurement 2 from sensor. S - - -
53 FlowMeasurement2 6 0.1 m
3
/h Flow measurement 3 from sensor. S - - -
58 SelectedFeedbackSensor 5 Enum
Read selected feedback sensor type
3: Flow sensor
6: Pressure sensor
●***---
Module Name
Data
type
Unit Description
MPC
Multi-E model G
Multi-E/TPED model H and later
MAGNA3-D