English (GB)
40
Hydro Multi-E/TPED model H
MAGNA3-D
Measured parameters
(Selected from display or Grundfos GO Remote)
Mapped to Modbus register
Parameter Analog input AI1, AI2, AI3
Temperature PT100
input T1, T2
Pump inlet pressure ● InletPressure (00315)
Pump inlet differential pressure ● InletDiffPressure (00356)
Pump outlet pressure ● OutletPressure (00341)
Pump outlet differential pressure ● OutletDiffPressure (00358)
Remote pressure 1 ● RemotePressure1 (00316)
Remote pressure 2 ● RemotePressure2 (00353)
Remote differential pressure ● RemoteDiffpressure (00359)
Feed tank level ● FeedTankLevel (00342)
Storage tank level ● StorageTankLevel (00350)
Pump flow ● VolumeFlow (00302)
Remote flow ● RemoteFlow (00360)
Temperature 1 ● ● RemoteTemp1 (00320)
Temperature 2 ● ● RemoteTemp2 (00354)
Ambient temperature ● ● AmbientTemp (00337)
Other parameter ● AuxSensorInput (00325)
Measured parameters
(Selected from display or Grundfos GO Remote)
Mapped to Modbus register
Parameter Analog input AI1, AI2, AI3
Temperature PT100
input T1, T2
Remote pressure 1 ● RemotePressure1 (00316)
Temperature 2 ● RemoteTemp2 (00354)