13
MAGNA3 INSULATED PUMPS INSTALLATION MANUAL
Start-Up
1. Make sure the grey start/stop jumper is installed as shown in figure 4. If not replace the start/stop jumper and apply power to the
pump.
NOTE: When the start/stop jumper is installed and power is connected the pump will start to run. If the start/stop jumper is installed
make sure the loop is filled, flushed and all valves are open as the pump will run.
2. After a few seconds (if the pump has not been powered previously), the pump display will change to the startup guide. The
startup guide will step through general settings such as language, date, and time (see Figure 14).
3. Once general settings are complete, press the home button, and set up the pump for the application.
4. Refer to Option 1 or 2 based upon application type (Constant Curve or Constant Pressure Mode).
CAUTION: VERIFY THAT AIR HAS BEEN PURGED FROM THE PIPING SYSTEM, AND THAT THE SYSTEM HAS
BEEN PRESSURIZED (IF APPLICABLE) BEFORE PROCEEDING.
Figure 14: Startup Screen
Figure 15: Control Panel