EasyManua.ls Logo

Grundfos MAGNA 25-100 - 10 Megging

Grundfos MAGNA 25-100
34 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
24
10. Megging
Megging of an installation incorporating a
GRUNDFOS MAGNA pump is not allowed, as the
built-in electronics may be damaged. If megging of
the pump is necessary, the pump should be
electrically separated from the installation.
Procedure:
Warning
Before removing the cables, the
electricity must be switched off.
Megging of the pump
Step Illustration Action
1
TM03 0908 0705
Switch off the electricity supply.
Open the connection box.
2
TM03 0909 0705
Remove the supply wires L and N and the earth
wire (PE).
3
TM03 0910 0705
Short-circuit the wires L and N using a wire.
Test between the wires L/N and earth (PE).
Test voltage: Max. 1000 VAC/1500 VDC.
Maximum permissible leakage current < 35 mA.
Note: Never test between the supply wires
(L and N).
4
TM03 0911 0705
Test the cable to the pump.
Pull the plug out of the pump and test again.
Refit the supply wires L and N and the earth wire
(PE).
Switch on the electricity supply.
PE
L/N
PE
L/N

Related product manuals