7. Priority of settings
The external forced-control signals will influence the settings available
on the pump control panel and with the R100. However, the pump can
always be set to max. curve duty or to stop on the control panel or with
the R100.
If two or more functions are activated at the same time, the pump will
operate according to the setting with the highest priority.
The priority of the settings is as shown in the table:
Example: If the pump has been forced to stop via an external signal, the
pump control panel or the R100 can only set the pump to max. curve.
Priority
Possible settings
Pump control panel
or R100
External signals
1Stop
2Max. curve–
3–Stop
4Min. curve–
5 Setpoint setting