Code Monitoring value Unit Scale ID Description
V2.6.4 Appl.StatusWord2 1 90
Bit coded status of application.
Values are visible as check boxes on
graphical keypad. If checked (x), the value
is active.
B0 = Acc/Dec prohibited
B1 = Motor switch open
B5 = Jockey pump active
B6 = Priming pump active
B7 = Input pressure supervision (Alarm/
Fault)
B8 = Frost protection (Alarm/Fault)
B9 = Autocleaning active
V2.6.5 DIN StatusWord1 1 56
16-bit word where each bit represents the
status of one digital input. 6 digital inputs
from every slot are read. Word 1 starts
from input 1 in slot A (bit0) and goes all the
way to input 4 in slot C (bit15).
V2.6.6 DIN StatusWord2 1 57
16-bit word where each bit represents the
status of one digital input. 6 digital inputs
from every slot are read. Word 1 starts
from input 5 in slot C (bit0) and goes all the
way to input 6 in slot E (bit13).
V2.6.7 MotCurrent1 deci. 0.1 45
Motor current monitor value with fixed
number of decimals and less filtering. Can
be used e.g. for fieldbus purposes to
always get the right value regardless of
frame size, or for monitoring when less
filtering time is needed for the motor
current.
V2.6.8 FreqRef Source 1 1495
Shows the momentary frequency
reference source.
0 = PC
1 = Preset Freqs
2 = Keypad Reference
3 = Fieldbus
4 = AI1
5 = AI2
6 = AI1+AI2
7 = PID Controller
8 = Motor Potentiometer
9 = Joystick
10 = Inching
100 = Not defined
101 = Alarm,PresetFreq
102 = Autocleaning
V2.6.9 LastActiveFaultCode 1 37
The fault code of latest activated fault that
has not been reset.
V2.6.10 LastActiveFault ID 1 95
The fault ID of latest activated fault that
has not been reset.