7.1.8 ExtPID Controller
Code Monitoring value Unit Scale ID Description
V2.9.1 ExtPID set point Varies
According to
P3.14.1.10
83
External PID controller setpoint value in
process units. Process unit is selected
with a parameter.
V2.9.2 ExtPID feedback Varies
According to
P3.14.1.10
84
External PID controller feedback value in
process units. Process unit is selected
with a parameter.
V2.9.3 ExtPID error Varies
According to
P3.14.1.10
85
External PID controller Error value.
Deviation of feedback from setpoint in
process units. Process unit is selected
with a parameter.
V2.9.4 ExtPID output % 0.01 86
External PID controller output in percent
(0..100 %). This value can be fed e.g. to
Analogue output.
V2.9.5 ExtPID status 1 87
0 = Stopped
1 = Running
4 = In dead band
7.1.9 Mainten. counters
Code Monitoring value Unit Scale ID Description
V2.11.1 MaintenCounter 1 h/ kRev Varies 1101
Status of maintenance counter in revolutions
multiplied by 1000, or hours.
For configuration and activation of this
counter, see chapter Group 3.16:
Maintenance counters.
7.1.10 Fieldbus data
Code Monitoring value Unit Scale ID Description
V2.12.1 FB Control Word 1 874
Fieldbus control word used by application in bypass
mode/format. Depending on the fieldbus type or profile
the data can be modified before sent to application.
V2.12.2 FB Speed Reference Varies 875
Speed reference scaled between minimum and
maximum frequency at the moment it was received by
the application. Minimum and maximum frequencies can
be changed after the reference was received without
affecting the reference.
V2.12.3 FB data in 1 1 876 Raw value of process data in 32-bit signed format
V2.12.4 FB data in 2 1 877 Raw value of process data in 32-bit signed format
V2.12.5 FB data in 3 1 878 Raw value of process data in 32-bit signed format
V2.12.6 FB data in 4 1 879 Raw value of process data in 32-bit signed format
V2.12.7 FB data in 5 1 880 Raw value of process data in 32-bit signed format
V2.12.8 FB data in 6 1 881 Raw value of process data in 32-bit signed format
V2.12.9 FB data in 7 1 882 Raw value of process data in 32-bit signed format
V2.12.10 FB data in 8 1 883 Raw value of process data in 32-bit signed format
70