8.1.3 Group 3.2: Start/Stop setup
Start/Stop commands are given differently depending
on the control place.
Remote control place (I/O A): Start, stop and
reverse commands are controlled by 2 digital inputs
chosen with parameters P3.5.1.1 and P3.5.1.2. The
functionality/logic for these inputs is then selected
with parameter P3.2.6 (in this group).
Remote control place (I/O B): Start, stop and
reverse commands are controlled by 2 digital inputs
chosen with parameters P3.5.1.4 and P3.5.1.5. The
functionality/logic for these inputs is then selected
with parameter P3.2.7 (in this group).
Local control place (Keypad): Start and stop
commands come from the keypad buttons, while the
direction of rotation is selected by the parameter
P3.3.1.9.
Remote control place (Fieldbus): Start, stop and
reverse commands come from fieldbus.
Code Parameter Min Max Unit Default ID Description
P3.2.1 Rem.Ctrl. Place 0 1 0 172
Selection of remote control place (start/
stop). Can be used to change back to
remote control from Grundfos PC tool
e.g. in case of a broken panel.
0 = I/O control
1 = Fieldbus control
P3.2.2 Local/Remote 0 1 0 211
Switch between local and remote control
places
0 = Remote
1 = Local
P3.2.3 Keypad stop button 0 1 0 114
0 = Stop button always enabled (Yes)
1 = Limited function of Stop button (No)
P3.2.4 Start function 0 1 0 505
0 = Ramping
1 = Flying start
P3.2.5 Stop function 0 2 0 506
0: coasting
1: ramp to min frequency
2: ramp to zero frequency
P3.2.6 I/O A start logic
0 4 1 300
Logic = 0:
Start sign 1 = Start Forward
Start sign 2 = Start Backward
Logic =1:
Start sign 1 = Start
Start sign 2 = Reverse
Logic = 2:
Double Start
Logic = 3:
Start sign 1 + Analogue sign
Logic = 4:
Solar only
P3.2.7 I/O B logic 0 4 1 363 See above.
P3.2.8 FB Start logic 0 1 0 889
0 = Rising edge required
1 = State