Group 3.5.2: Analog inputs
The number of usable analogue inputs
depends on your (option) board setup. The
standard I/O board embodies 2 analogue
inputs.
Group 3.5.2.1: Analog Input 1
Code Parameter Min Max Unit Default ID Description
P3.5.2.1.1 AI1 signal selection
AnIN
SlotA.1
377
Connect the AI1 signal to the
analogue input of your choice
with this parameter.
Programmable. See Group
3.1: Motor settings.
P3.5.2.1.2 AI1 signal filter time 0.00 300.00 s 0.1 378 Filter time for analogue input.
P3.5.2.1.3 AI1 signal range 0 1 0 379
0 = 0…10 V / 0…20 mA
1 = 2…10 V / 4…20 mA
P3.5.2.1.4 AI1 custom. min -160.00 160.00 % 0.00 380
Custom range min setting
20 % = 4-20 mA / 2-10 V
P3.5.2.1.5 AI1 custom. max -160.00 160.00 % 100.00 381 Custom range max setting
P3.5.2.1.6 AI1 signal inversion 0 1 0 387
0 = Normal
1 = Signal inverted
Group 3.5.2.2: Analog Input 2
Code Parameter Min Max Unit Default ID Description
P3.5.2.2.1 AI2 signal selection
AnIN
SlotA.2
388 See P3.5.2.1.1.
P3.5.2.2.2 AI2 signal filter time 0.00 300.00 s 0.1 389 See P3.5.2.1.2.
P3.5.2.2.3 AI2 signal range 0 1 1 390 See P3.5.2.1.3.
P3.5.2.2.4 AI2 custom. min -160.00 160.00 % 0.00 391 See P3.5.2.1.4.
P3.5.2.2.5 AI2 custom. max -160.00 160.00 % 100.00 392 See P3.5.2.1.5.
P3.5.2.2.6 AI2 signal inversion 0 1 0 398 See P3.5.2.1.6.
Group 3.5.2.3: Analog Input 3
Code Parameter Min Max Unit Default ID Description
P3.5.2.3.1AI3 signal selection
AnIN
SlotD.1
141 See P3.5.2.1.1
P3.5.2.3.2 AI3 signal filter time 0.00 300.00 s 0.1 142 See P3.5.2.1.2.
P3.5.2.3.3 AI3 signal range 0 1 0 143 See P3.5.2.1.3.
P3.5.2.3.4 AI3 custom. min -160.00 160.00 % 0.00 144 See P3.5.2.1.4.
P3.5.2.3.5 AI3 custom. max -160.00 160.00 % 100.00 145 See P3.5.2.1.5.
P3.5.2.3.6 AI3 signal inversion 0 1 0 151 See P3.5.2.1.6.
89