8.1.7 Group 3.6: Fieldbus DataMap
Code Parameter Min Max Unit Default ID Description
P3.6.1 FB DataOut 1 Sel 0 35000 1 852
Data sent to fieldbus can be
chosen with parameter and
monitor value ID numbers.
The data is scaled to
unsigned 16-bit format
according to the format on
keypad. E.g. 25.5 on keypad
equals 255.
P3.6.2 FB DataOut 2 Sel 0 35000 2 853
Select Process Data Out with
parameter ID
P3.6.3 FB DataOut 3 Sel 0 35000 3 854
Select Process Data Out with
parameter ID
P3.6.4 FB DataOut 4 Sel 0 35000 4 855
Select Process Data Out with
parameter ID
P3.6.5 FB DataOut 5 Sel 0 35000 5 856
Select Process Data Out with
parameter ID
P3.6.6 FB DataOut 6 Sel 0 35000 6 857
Select Process Data Out with
parameter ID
P3.6.7 FB DataOut 7 Sel 0 35000 7 858
Select Process Data Out with
parameter ID
P3.6.8 FB DataOut 8 Sel 0 35000 37 859
Select Process Data Out with
parameter ID
Fieldbus process data out
Default values for Process Data Out to monitor
through fieldbus are listed in the table below.
Data Value Scale
Process Data Out 1 Output frequency 0.01 Hz
Process Data Out 2 Motor speed 1 rpm
Process Data Out 3 Motor current 0.1 A
Process Data Out 4 Motor torque 0.1 %
Process Data Out 5 Motor power 0.1 %
Process Data Out 6 Motor voltage 0.1 V
Process Data Out 7 DC-link voltage 1 V
Process Data Out 8 Last active fault code 1
Example: Value "2500" for Output Frequency
corresponds to "25.00 Hz" (scaling value is 0.01).
All monitoring values listed in chapter Monitoring
menu are given the scaling value.