Group 3.5.4: Analogue outputs
Group 3.5.4.1: Slot A Basic
Code Parameter Min Max Unit Default ID Description
P3.5.4.1.1 AO1 function 0 19 2 10050
0 = TEST 0 % (Not used)
1 = TEST 100 %
2 = Output freq (0-fmax)
3 = Freq reference (0-fmax)
4 = Motor speed (0 - Motor nominal
speed)
5 = Output current (0-I
nMotor
)
6 = Motor torque (0-T
nMotor
)
7 = Motor power (0-P
nMotor
)
8 = Motor voltage (0-U
nMotor
)
9 = DC link voltage (0-1000 V)
10 = PID1 output (0-100 %)
11 = Ext.PID output (0-100 %)
12 = ProcessDataIn1 (0-100 %)
13 = ProcessDataIn2 (0-100 %)
14 = ProcessDataIn3 (0-100 %)
15 = ProcessDataIn4 (0-100 %)
16 = ProcessDataIn5 (0-100 %)
17 = ProcessDataIn6 (0-100 %)
18 = ProcessDataIn7 (0-100 %)
19 = ProcessDataIn8 (0-100 %)
P3.5.4.1.2 AO1 filter time
0.0 300.0 s 1.0 10051
Filtering time of analogue output
signal. See P3.5.2.1.2
0 = No filtering
P3.5.4.1.3 AO1 minimum 0 1 0 10052
0 = 0 mA / 0 V
1 = 4 mA / 2 V
Signal type (current/voltage)
selected with dip switches.
Note the difference in analogue
output scaling in parameter
P3.5.4.1.4.
See also parameter P3.5.2.1.3.
P3.5.4.1.4 AO1 minimum scale Varies Varies Varies 0.0 10053
Min scale in process unit (depends
on selection of AO1 function).
P3.5.4.1.5 AO1 maximum scale Varies Varies Varies 0.0 10054
Max scale in process unit (depends
on selection of AO1 function)
Expander slots D to E analogue outputs
Shows only parameters for existing outputs on option
boards placed in slots D and E. Selections as in
Standard AO1 (P3.5.4.1.1).
This group or these parameters are not visible if no
digital outputs exist in slots D or E.
Related information
6.2.5 I/O and hardware