8.1.8 Group 3.7: Prohibit Frequencies
In some systems it may be necessary to avoid certain
frequencies due to mechanical resonance problems.
By setting up prohibit frequencies it is possible to skip
these ranges. When the (input) frequency reference
is increased, the internal frequency reference is kept
at the low limit until the (input) reference is above the
high limit.
Code Parameter Min Max Unit Default ID Description
P3.7.1 Range 1 Low Lim -1,00 320,00 Hz 0,00 509 0 = Not used
P3.7.2 Range 1 High Lim 0,00 320,00 Hz 0,00 510 0 = Not used
P3.7.3 Range 2 Low Lim 0,00 320,00 Hz 0,00 511 0 = Not used
P3.7.4 Range 2 High Lim 0,00 320,00 Hz 0,00 512 0 = Not used
P3.7.5 Range 3 Low Lim 0,00 320,00 Hz 0,00 513 0 = Not used
P3.7.6 Range 3 High Lim 0,00 320,00 Hz 0,00 514 0 = Not used
P3.7.7 RampTimeFactor 0,1 10,0 Times 1,0 518
Multiplier of the currently
selected ramp time between
prohibit frequency limits.
8.1.9 Group 3.8: Supervisions
Choose here:
1. one or two (P3.8.1/P3.8.5) signal values for
supervision.
2. whether the low or high limits are supervised
(P3.8.2/P3.8.6)
3. the actual limit values (P3.8.3/P3.8.7).
4. the hystereses for the set limit values (P3.8.4/
P3.8.8).
Code Parameter Min Max Unit Default ID Description
P3.8.1 Superv1 Item 0 11 0 1431
0 = Output frequency
1 = Frequency reference
2 = Motor current
3 = Motor torque
4 = Motor power
5 = DC-link voltage
6 = Analogue input 1
7 = Analogue input 2
8 = Analogue input 3
9 = Analogue input 4
10 = Analogue input 5
11 = Analogue input 6
P3.8.2 Superv1 Mode 0 2 0 1432
0 = Not used
1 = Low limit supervision
(output active under limit)
2 = High limit supervision
(output active over limit)
P3.8.3 Superv1 Limit -50.00 50.00 Varies 25.00 1433
Supervision limit for selected item. Unit appears
automatically.
P3.8.4 Superv1 Hyst 0.00 50.00 Varies 5.00 1434
Supervision limit hysteresis for selected item.
Unit is set automatically.
P3.8.5 Superv2 Item 0 11 1 1435 See P3.8.1