Code Parameter Min Max Unit Default ID Description
P3.8.6 Superv2 Mode 0 2 0 1436 See P3.8.2
P3.8.7 Superv2 Limit -50.00 50.00 Varies 40.00 1437 See P3.8.3
P3.8.8 Superv2 Hyst 0.00 50.00 Varies 5.00 1438 See P3.8.4
8.1.10 Group 3.9: Protections
Group 3.9.1: General
Code Parameter Min Max Unit Default ID Description
P3.9.1.2 External Fault 0 3 2 701
0 = No action
1 = Alarm
2 = Fault (Stop according to
stop mode)
3 = Fault (Stop by coasting)
P3.9.1.3 InputPhase Fault 0 1 1 730
0= 3 Phases support
1= 1 Phase support
P3.9.1.4 Undervoltage Flt 0 1 0 727
0 = Fault stored in history
1 = Fault not stored in history
P3.9.1.5 OutputPhase Flt 0 3 2 702 See P3.9.1.2
P3.9.1.6 FieldbusComm Flt 0 4 3 733
0 = No action
1 = Alarm
2 = Alarm, PresetFreq
3 = Fault (Stop according to
stop mode)
4 = Fault (Stop by coasting)
P3.9.1.7 SlotComm Flt 0 3 2 734 See P3.9.1.2
P3.9.1.8 Thermistor Fault 0 3 0 732 See P3.9.1.2
P3.9.1.9 PID SoftFill Fault 0 3 2 748 See P3.9.1.2
P3.9.1.10 PID Supervision 0 3 2 749 See P3.9.1.2
P3.9.1.11 ExtPID Supervision 0 3 2 757 See P3.9.1.2
P3.9.1.13 PresetAlarmFreq P3.3.1.1 P3.3.1.2 Hz 25.00 183
This frequency used when
fault response (in Group 3.9:
Protections) is Alarm+preset
frequency
P3.9.1.14 STO Fault 0 3 3 775
Defines drive operation when
STO function has been
activated (eg. Emergency
stop button has been
pressed).
96